ABC Cable Triplex Service Drop AAC/XLPE+ACSR Janthina


                                 ABC Cable Triplex Service Drop AAC/XLPE+ACSR Janthina

Basis Info

Modell Nr..
ABC CABLE

Art
Isolierte

Leitertyp
Stranded

Anwendung
Oben

Leitermaterial
Aluminium

Isoliermaterial
XLPE

Material Form
Runddraht

Bescheinigung
ISO9001 ,
CE ,
UL ,
CCC ,
RoHS ,
VDE

Zusätzliche Informationen.

Warenzeichen
Huatong

Verpackung
Drum Coil

Standard
drum

Herkunft
China

HS-Code
8544492100

Produktionskapazität
100000km/Month

Produktbeschreibung

ABC CABLE -aerial bundle cable :are mainly used for electric power transmission, rebuiding of urban and forest regions. They can improves safety and reliance of electrified wire netting.

1 Type:Duplex Service Drop, Triplex Service Drop, Quadruplex Service Drop
Duplex Service Drop
   Applications:To supply 120 volt aerial service for temporary service at construction sites,outdoor or street lighting . For service at 600 volts or lower at a conductor temperature of 75 maximum.

Triplex Service Drop
   Applications: To supply power from the ulility`s lines to the consumer`s weatherhead. For service at 600 volts or less(phase to phase ) at a conductor temperature of 75 maximum for PE insulation or 90 maximum for XLPE insulation .

Service Drop
    Applications: Used to supply 3 phase power , usually from a pole-mounted transformer to the use`s servic head where connection to the service entance cable is made . To be used at voltages of 600 volts or less phase to phase and at conductor temperature not to exceed 75 for PE insulated conductors or 90 for XLPE insulated conductors.

2  Construction
     a Phase Conductor construction:The phase conductor is aluminum alloy 1350-H19 hard-drawn, compressed concentric-lay-stranded.
    b  Neutral Conductor Construction
Cable assemblies are available with the following neutral conductors:
Aluminum conductors, coated-steel reinforced (ACSR), concentric-lay-stranded
Aluminum alloy 1350-H19 hard-drawn, concentric-lay-stranded
Aluminum alloy 6201-T81, concentric-lay-stranded
    c Insulation Material
The standard insulation on the phase conductor is black low-density crosslinked polyethylene (XLPE)
Alternatively, black linear low-density polyethylene (LLDPE) insulation with a 75°C temperature rating is available upon request.

3 specification
    see following table
4.Standards
1. B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
2. B-231 Aluminum Conductors, Concentric-Lay-Stranded.
3. B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR).
4. B-399 Concentric-Lay_Stranded 6201-T81 Aluminum Alloy Conductors.
5. B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
6. Duplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76

Duplex Service Drop

Code
word
AWG or kcmil Bare Neutral Messenger Phase conductor Weight
Kg/km
Allowcable
Ampacities(A)
ACSR Rated
Strength
Lbs.
AAC Insul
Thick.mm
XLPE PE
Number Dia.
mm
Number Dia.mm Number Dia.mm
Setter
Shepherd
Eskimo
Terrier
Chow
Bull
1*6AWG+1*6AWG
1*6AWG+1*6AWG
1*4AWG+1*4AWG
1*4AWG+1*4AWG
1*2AWG+1*2AWG
1*1/0AWG+1*1/0AWG
1
1
1
1
1
1
1.68
1.68
2.12
2.12
2.67
3.37
6
6
6
6
6
6
1.68
1.68
2.12
2.12
2.67
3.37
1190
1190
1860
1860
2850
4380
1
7
1
7
7
19
4.11
1.56
5.19
1.96
2.47
1.89
1.14
1.14
1.14
1.14
1.14
1.52
111
113
171
173
266
427
85
85
115
115
150
205
70
70
90
90
120
160

Triplex ABC Cable

Code*Word Phase conductor Bare Neutral Message Nominal lay Length Weight Per 1000 ft.(lbs.) Allo wable Amp acitles
Size (A WG) Stranding Insul Thick(Mils) Size (AWG) Stranding Rated Strength (lbs.) inches XLP POLY XLP POLY
AAC Neutral-messenger
Pateela 6 7 45 6 7 563 14.88 103 103 85 70
Oyster 4 7 45 4 7 881 14.88 154 154 115 90
Clam 2 7 45 2 7 1350 20.58 233 233 150 120
Murex 1/0 7 60 1/0 7 1990 20.58 374 374 205 160
Purpura 1/0 9 60 1/0 7 1990 20.58 368 368 205 160
Nassa 2/0 7 60 2/0 7 2510 25.42 462 462 235 185
Melita 3/0 17 60 3/0 19 3310 29.97 562 562 275 215
Portunus 4/0 18 60 4/0 19 4020 29.97 696 696 315 245
Nannynose 336.4 19 60 336.4 19 6146 38.79 1118 1118 420 325
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP) +Conductor temperature of 90 for XLP,75 for Poly;ambient temperature of 40;emissivity 0.2;2ft./sec.Wind in sun.

QuadruplexABC Cable

Code*Word Phase conductor Bare Neutral Message Nominal lay Length Weight Per 1000 ft.(lbs.) Allo wable Amp acitles
Size (A WG) Stranding Insul Thick(Mils) Size (AWG) Stranding Rated Strength (lbs.) inches XLP POLY XLP POLY
AAC Neutral-messenger
Clydessdale 4 1 45 4 7 881 20.58 198 198 100 80
Pinto 4 7 45 4 7 881 20.58 211 211 100 80
Mustang 2 7 45 2 7 1350 25.42 318 318 135 105
Criollo 1/0 9 60 1/0 7 1990 25.42 503 503 180 140
Percheron 2/0 11 60 2/0 7 2510 29.97 619 619 205 160
Hanovarian 3/0 17 60 3/0 19 3310 35.18 764 764 235 185
Oldenburg 4/0 18 60 4/0 19 4020 35.18 945 945 275 210
Lippizaner 336.4 19 80 336.4 19 6146 38.79 1519 1519 370 280
*Code words for XLP insulated products are formed by adding "/XLP" to the conventional code words above (e.g.-Chihuahua/XLP) +Conductor temperature of 90 for XLP,75 for Poly;ambient temperature of 40;emissivity 0.2;2ft./sec.