Kabel Mit Isolierter Antenne ABC-PVC/XLPE für werkseitigen Preis
Basis Info
Modell Nr..
Aerial Bundled Cable
Art
Isolierte
Leitertyp
Stranded
Anwendung
Oben ,
U-Bahn
U-Bahn
Leitermaterial
Aluminium
Isoliermaterial
XLPE
Material Form
Runddraht
Bescheinigung
ISO9001 ,
CE ,
CCC ,
RoHS
CE ,
CCC ,
RoHS
Zusätzliche Informationen.
Warenzeichen
Huatong
Verpackung
All Wooden, Steel Wooden or Steel Package
Herkunft
China
HS-Code
8544492100
Produktionskapazität
5000tons /Month
Produktbeschreibung
ABC-PVC/XLPE Insulated Aerial Bundled Cable for factory price
1. Application
0.6/1KV AAC/AAAC/ACSR XLPE/PE Insulation ABC cable AAAC conductor has been widely used in power transmission lines and electricity distribution lines with various voltage levels, because they have such good characteristics as simple structure, convenient installation and maintenance, low cost large transmission capacity. And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
2. Standard
We can produce as per the standard of GB, IEC, ASTM,DIN,CSA,JIS and also particularly customize and manufacture according to your special requirement.
Standards / Testing Specifications
IEC 61089, BS 3242, DIN 48201, ASTM B399, BS EN50183, GB/T 1179-2008
Working conditions aerial insulation power cable
1) Rated voltage: 0.6kV/1Kv
2) The tallest working temperature of the cable conductor; XLPE insulation cable: 90°C;
HDPE insulation cable: 75°C;
3) During having a short (lasting less than 5 seconds) the maximum temperature;
XLPE insulated cables is 250°C;
HDPE insulated cable is 150°C
4) During the cable lying, the ambient temperature must be above-20°C
5) Bending radius allowance of the cable;
A)1Kv aerial insulation power cable:
It should be no less than 4D for the cable with outer diameter less than 25mm;
It should be no less than 6D for the cable with outer diameter of 25mm or more;
B) 10kV aerial insulation power cable:
Single core cable: 20 (D+d)±5%mm;
Multi-core cable:15 (D+d)±%mm
Formula inside: D-Actual cable outer diameter;
d-Actual conductor outer diameterl
Standard Packaging
As provided by standards and customer’s requirement.
1. Application
0.6/1KV AAC/AAAC/ACSR XLPE/PE Insulation ABC cable AAAC conductor has been widely used in power transmission lines and electricity distribution lines with various voltage levels, because they have such good characteristics as simple structure, convenient installation and maintenance, low cost large transmission capacity. And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
2. Standard
We can produce as per the standard of GB, IEC, ASTM,DIN,CSA,JIS and also particularly customize and manufacture according to your special requirement.
Standards / Testing Specifications
IEC 61089, BS 3242, DIN 48201, ASTM B399, BS EN50183, GB/T 1179-2008
Working conditions aerial insulation power cable
1) Rated voltage: 0.6kV/1Kv
2) The tallest working temperature of the cable conductor; XLPE insulation cable: 90°C;
HDPE insulation cable: 75°C;
3) During having a short (lasting less than 5 seconds) the maximum temperature;
XLPE insulated cables is 250°C;
HDPE insulated cable is 150°C
4) During the cable lying, the ambient temperature must be above-20°C
5) Bending radius allowance of the cable;
A)1Kv aerial insulation power cable:
It should be no less than 4D for the cable with outer diameter less than 25mm;
It should be no less than 6D for the cable with outer diameter of 25mm or more;
B) 10kV aerial insulation power cable:
Single core cable: 20 (D+d)±5%mm;
Multi-core cable:15 (D+d)±%mm
Formula inside: D-Actual cable outer diameter;
d-Actual conductor outer diameterl
Standard Packaging
As provided by standards and customer’s requirement.
BS7884-1997 | |||||
Nominal Area | Stranding | Diameter of conductor | Linear mass | Rated strength | D.C. resistance at 20°C |
mm2 | No./mm | mm | Kg/km | KN | Ω/km |
10 | 7/1.35 | 4.05 | 89.82 | 3.752 | 1.829 |
14 | 7/1.6 | 4.8 | 126.2 | 5.627 | 1.30300 |
16 | 3/2.65 | 5.72 | 148.30 | 6.194 | 1.10600 |
16 | 7/1.7 | 5.10 | 142.40 | 5.946 | 1.15400 |
25 | 7/2.1 | 6.30 | 217.30 | 9.073 | 0.75630 |
32 | 3/3.75 | 8.10 | 296.90 | 12.4 | 0.55200 |
32 | 7/2.46 | 7.38 | 298.20 | 12.442 | 0.54970 |
35 | 7/2.5 | 7.50 | 308.00 | 12.86 | 0.53370 |
50 | 7/3.00 | 9.00 | 443.50 | 18.52 | 0.37060 |
50 | 19/1.8 | 9.00 | 435.80 | 17.7 | 0.38190 |
70 | 7/3.55 | 10.65 | 621.10 | 25.93 | 0.26460 |
70 | 19/2.1 | 10.50 | 593.20 | 24.09 | 0.28060 |
95 | 19/2.5 | 12.50 | 840.70 | 34.14 | 0.19800 |
100.0 | 7/4.3 | 12.90 | 911.20 | 36.54 | 0.18100 |
120.0 | 19/2.8 | 14.00 | 1055.00 | 42.83 | 0.15780 |
125.0 | 19/2.9 | 14.50 | 1131.00 | 45.94 | 0.14710 |
150.0 | 19/3.2 | 16.00 | 1377.00 | 55.94 | 0.12080 |
150.0 | 37/2.25 | 15375.00 | 1334.00 | 53.88 | 0.12640 |
185.0 | 19/3.55 | 17.75 | 1695.00 | 68.86 | 0.09815 |
185.0 | 37/2.5 | 17.75 | 1647.00 | 66.49 | 0.10240 |
Phase | Phase | Phase | Approx.Overall Diameter | Max. D.C. Resistance of Conductor at 20 Centigrade | |||
AAC+UV-XLPE | Compact Conductor | UV-XLPE Insulation | |||||
No.X Normal Cross Section of Cores | No.of Al Wires | Overall Diameter | Normal Thickness | Min. | Diameter | ||
No. X mm 2 | – | mm | mm | mm | mm | mm | ohm/km |
1 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 6.05 | 3.08 |
1 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 7.20 | 1.91 |
1 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 8.40 | 1.20 |
1 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 9.80 | 0.868 |
1 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 11.10 | 0.641 |
1 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 12.60 | 0.443 |
1 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 14.80 | 0.320 |
1 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 16.20 | 0.253 |
1 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 18.20 | 0.206 |
1 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 20.20 | 0.164 |
1 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 22.80 | 0.125 |
2 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 12.10 | 3.08 |
2 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 14.40 | 1.91 |
2 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 16.80 | 1.20 |
2 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 19.60 | 0.868 |
2 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 22.20 | 0.641 |
2 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 25.20 | 0.443 |
2 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 29.60 | 0.320 |
2 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 32.40 | 0.253 |
2 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 36.40 | 0.206 |
2 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 40.40 | 0.164 |
2 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 45.60 | 0.125 |
3 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 13.07 | 3.08 |
3 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 15.55 | 1.91 |
3 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 18.14 | 1.20 |
3 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 21.17 | 0.868 |
3 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 23.98 | 0.641 |
3 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 27.22 | 0.443 |
3 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 31.97 | 0.320 |
3 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 34.99 | 0.253 |
3 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 39.31 | 0.206 |
3 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 43.63 | 0.164 |
3 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 49.25 | 0.125 |
4 X 10 | 7 | 4.05 | 1.0 | 0.8 | 6.05 | 14.64 | 3.08 |
4 X 16 | 7 | 4.8 | 1.2 | 0.98 | 7.2 | 17.42 | 1.91 |
4 X 25 | 7 | 6 | 1.2 | 0.98 | 8.4 | 20.33 | 1.20 |
4 X 35 | 7 | 7.0 | 1.4 | 1.16 | 9.8 | 23.72 | 0.868 |
4 X 50 | 7 | 8.3 | 1.4 | 1.16 | 11.1 | 26.86 | 0.641 |
4 X 70 | 19 | 9.8 | 1.4 | 1.16 | 12.6 | 30.49 | 0.443 |
4 X 95 | 19 | 11.6 | 1.6 | 1.34 | 14.8 | 35.82 | 0.320 |
4 X 120 | 19 | 13 | 1.6 | 1.34 | 16.2 | 39.20 | 0.253 |
4 X 150 | 19 | 14.6 | 1.8 | 1.52 | 18.2 | 44.04 | 0.206 |
4 X 185 | 36 | 16.2 | 2.0 | 1.70 | 20.2 | 48.88 | 0.164 |
4 X 240 | 36 | 18.4 | 2.2 | 1.88 | 22.8 | 55.18 | 0.125 |
Construction of twisted abc cable
Conductors are concentrically stranded, compressed 1350 H-19 aluminum. Insulated with either polyethylene or cross-linked polyethylene (XLPE). Neutral messengers are concentrically stranded 6201, AAC, or ACSR.
Type | Specification | Conductor | Insulation | Cable Dia | kg/km | |||||
Nomina Diameter | No. | Conductor Dia. | Thickness | Overall Dia. | mm | Aluminium | XLPE | kg/km | ||
ABC | 2*10 | 1.35 | 7 | 4 | 1 | 6 | 12 | 55.478 | 32.284 | 87.762 |
2*16 | 1.7 | 7 | 4.9 | 1.2 | 7.3 | 14.6 | 87.974 | 46.805 | 134.779 | |
2*25 | 2.12 | 7 | 6 | 1.2 | 8.4 | 16.8 | 136.813 | 55.176 | 191.989 | |
2*35 | 2.52 | 7 | 7 | 1.4 | 9.8 | 19.6 | 193.311 | 74.598 | 267.909 | |
2*50 | 3 | 7 | 8.4 | 1.4 | 11.2 | 22.4 | 273.967 | 86.958 | 360.925 | |
2*70 | 2.52 | 14 | 10 | 1.4 | 12.8 | 25.6 | 386.622 | 101.083 | 487.705 | |
2*70 | 2.54 | 14 | 10 | 1.4 | 12.8 | 25.6 | 392.783 | 101.083 | 493.866 | |
2*70 | 2.72 | 12 | 10 | 1.4 | 12.8 | 25.6 | 386.079 | 101.083 | 487.162 | |
2*95 | 2.52 | 19 | 11.5 | 1.6 | 14.7 | 29.4 | 524.702 | 132.104 | 656.805 | |
2*120 | 2.85 | 19 | 12.9 | 1.6 | 16.1 | 32.2 | 671.121 | 146.168 | 817.289 | |
2*120 | 2.54 | 24 | 12.9 | 1.6 | 16.1 | 32.2 | 673.343 | 146.168 | 819.511 | |
2*150 | 2.58 | 30 | 14.5 | 1.8 | 18.1 | 36.2 | 868.397 | 184.160 | 1052.556 | |
2*170 | 3.38 | 19 | 15.5 | 2 | 19.5 | 39 | 943.941 | 219.046 | 1162.987 | |
2*170 | 2.52 | 37 | 15.5 | 2 | 19.5 | 39 | 1021.787 | 219.046 | 1240.833 | |
2*185 | 2.58 | 37 | 16.1 | 2 | 20.1 | 40.2 | 1071.023 | 226.535 | 1297.558 | |
2*240 | 2.96 | 37 | 18.3 | 2.2 | 22.7 | 45.4 | 1409.752 | 281.513 | 1691.266 | |
2*300 | 2.58 | 60 | 20.5 | 2.2 | 24.9 | 49.8 | 1736.794 | 311.651 |
- Next: (Trapezoidal Shaped) ACSR/Tw Aluminium Conductor
- Previous: Guy Wire/ Galvanized Steel Wire/ Stay Wire Gi ASTM A475