6.35/10kv XLPE Insulated Power Cable

 6.35/10kv XLPE Insulated Power Cable

Produktdetails

Basis Info

Modell Nr.:YJV/YJV22/YJV32
Anwendung: Bau , U-Bahn
Spannung: Nieder-und Mittelspannung Kabel
Strom: AC-Kabel
Isoliermaterial: XLPE
Bescheinigung: ISO , CE

Zusätzliche Informationen.

Warenzeichen:Jiapu
Verpackung:Wooden Drum or Wooden&Steel Drum
Standard:IEC, ASTM, DIN, BS, GB, Any standard
Herkunft:Henan China
HS-Code:4101962331
Produktionskapazität:5000km/Month

Produktbeschreibung

6.35/10kV XLPE Insulated Power Cable

Application:
Media Voltage XLPE Insulated power cable is used to transmit and distribute power in power transmission and distribution system of 35kV or lower. It is generally applied to the fields including power, construction, mines, metallurgy, petrochemical industry and communication in complete replace of oil immersed paper insulated power cable.

Prpperty:
1.The highest allowed operating temperature of conductor for long-term working is 90 degrees.
2.In short circuit (Max long term is no more than 5 seconds). The highest temperature for conductor is no more than 250 degrees.
3.The cable is laid without horizontal drop limit. The environment temperature should be no lower than 0 when lay. Otherwise it should be preheated.
4.Excellent electrical performance, resistance to chemical corrosion.
5.They can stand advisable traction when laid.They can stand traction from Outside.Left low smoke halogen-free after burned.Retard the burning of the cable.

Specification:

Standard:
IEC60502,designing and manufacturing special power cable according to the other standards required by the customers.

1)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of
Copper Tape
Normal Thickness of Outer Sheath Approx.
Overall Dia.
Approx. Net Weight Max. D.C. Resistance of Conductor at 20ºC
Al Conductor Cu Conductor Al Conductor Cu Conductor
mm2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25 6.0 2.5 0.12 1.5 17.6 0.34 0.49 1.2000 0.7270
35 7.0 2.5 0.12 1.5 18.5 0.39 0.60 0.8680 0.5240
50 8.3 2.5 0.12 1.6 20.0 0.46 0.74 0.6410 0.3870
70 9.7 2.5 0.12 1.6 21.5 0.55 0.96 0.4430 0.2680
95 11.3 2.5 0.12 1.7 23.3 0.66 1.23 0.3200 0.1930
120 13 2.5 0.12 1.7 24.8 0.77 1.48 0.2530 0.1530
150 14.6 2.5 0.12 1.8 26.4 0.87 1.77 0.2060 0.1240
185 15.9 2.5 0.12 1.8 28.1 1.01 2.13 0.1640 0.0991
240 18.3 2.6 0.12 1.9 30.9 1.23 2.71 0.1250 0.0754
300 20.4 2.8 0.12 2.0 33.6 1.48 3.32 0.1000 0.0601
400 23.2 3.0 0.12 2.1 37.0 1.81 4.16 0.0778 0.0470
500 26.4 3.2 0.12 2.2 41.1 2.24 5.27 0.0605 0.0366
630 30.1 3.2 0.12 2.3 45.0 2.73 6.62 0.0469 0.0283

2)6/10(12)kV,6.35/11(12)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of
Copper Tape
Normal Thickness of Outer Sheath Approx.
Overall Dia.
Approx. Net Weight Max. D.C. Resistance of Conductor at 20ºC
Al Conductor Cu Conductor Al Conductor Cu Conductor
mm2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25 6.0 3.4 0.12 1.5 19.4 0.40 0.55 1.2000 0.7270
35 6.9 3.4 0.12 1.6 20.5 0.45 0.66 0.8680 0.5240
50 8.2 3.4 0.12 1.6 21.8 0.52 0.80 0.6410 0.3870
70 9.7 3.4 0.12 1.7 23.5 0.62 1.03 0.4430 0.2680
95 11.3 3.4 0.12 1.7 25.1 0.73 1.30 0.3200 0.1930
120 12.8 3.4 0.12 1.8 26.8 0.85 1.56 0.2530 0.1530
150 14.2 3.4 0.12 1.8 28.2 0.95 1.85 0.2060 0.1240
185 15.9 3.4 0.12 1.9 30.1 1.10 2.22 0.1640 0.0991
240 18.3 3.4 0.12 2.0 32.7 1.33 2.80 0.1250 0.0754
300 20.4 3.4 0.12 2.0 34.8 1.54 3.39 0.1000 0.0601
400 23.2 3.4 0.12 2.2 38.0 1.87 4.22 0.0778 0.0470
500 26.4 3.4 0.12 2.2 41.5 2.26 5.29 0.0605 0.0366
630 30.1 3.4 0.12 2.4 45.6 2.78 6.67 0.0469 0.0283

3)8.7/10(15)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of
Copper Tape
Normal Thickness of Outer Sheath Approx.
Overall Dia.
Approx. Net Weight Max. D.C. Resistance of Conductor at 20ºC
Al Conductor Cu Conductor Al Conductor Cu Conductor
mm2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25 6.0 4.5 0.12 1.6 21.8 0.48 0.63 1.2000 0.7270
35 6.9 4.5 0.12 1.7 22.9 0.54 0.75 0.8680 0.5240
50 8.2 4.5 0.12 1.7 24.2 0.61 0.89 0.6410 0.3870
70 9.7 4.5 0.12 1.8 25.9 0.72 1.13 0.4430 0.2680
95 11.3 4.5 0.12 1.8 27.5 0.84 1.40 0.3200 0.1930
120 12.8 4.5 0.12 1.9 29.2 0.96 1.67 0.2530 0.1530
150 14.2 4.5 0.12 1.9 30.6 1.06 1.96 0.2060 0.1240
185 15.9 4.5 0.12 2.0 32.5 1.22 2.34 0.1640 0.0991
240 18.3 4.5 0.12 2.1 35.1 1.46 2.93 0.1250 0.0754
300 20.4 4.5 0.12 2.1 37.2 1.68 3.52 0.1000 0.0601
400 23.2 4.5 0.12 2.2 40.2 2.00 4.35 0.0778 0.0470
500 26.4 4.5 0.12 2.3 43.9 2.43 5.45 0.0605 0.0366
630 30.1 4.5 0.12 2.4 47.8 2.93 6.83 0.0469 0.0283

4)12/20(24)kV, 12.7/22(24)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of
Copper Tape
Normal Thickness of Outer Sheath Approx.
Overall Dia.
Approx. Net Weight Max. D.C. Resistance of Conductor at 20ºC
Al Conductor Cu Conductor Al Conductor Cu Conductor
mm2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25
35 6.9 5.5 0.12 1.7 24.9 0.62 0.83 0.8680 0.5240
50 8.2 5.5 0.12 1.8 26.4 0.70 0.98 0.6410 0.3870
70 9.7 5.5 0.12 1.8 27.9 0.80 1.21 0.4430 0.2680
95 11.3 5.5 0.12 1.9 29.7 0.94 1.50 0.3200 0.1930
120 12.8 5.5 0.12 1.9 31.2 1.05 1.77 0.2530 0.1530
150 14.2 5.5 0.12 2.0 32.8 1.17 2.07 0.2060 0.1240
185 15.9 5.5 0.12 2.0 34.5 1.33 2.45 0.1640 0.0991
240 18.3 5.5 0.12 2.1 37.1 1.57 3.04 0.1250 0.0754
300 20.4 5.5 0.12 2.2 39.4 1.81 3.66 0.1000 0.0601
400 23.2 5.5 0.12 2.3 42.4 2.14 4.49 0.0778 0.0470
500 26.4 5.5 0.12 2.4 46.1 2.58 5.61 0.0605 0.0366
630 30.1 5.5 0.12 2.4 49.8 3.10 6.99 0.0469 0.0283

5)18/30(36)kV,19/33(36)kV,Single Core,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of
Copper Tape
Normal Thickness of Outer Sheath Approx.
Overall Dia.
Approx. Net Weight Max. D.C. Resistance of Conductor at 20ºC
Al Conductor Cu Conductor Al Conductor Cu Conductor
mm2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25
35
50 8.2 8.0 0.12 2.0 31.8 0.95 1.23 0.6410 0.3870
70 9.7 8.0 0.12 2.0 33.3 1.07 1.47 0.4430 0.2680
95 11.3 8.0 0.12 2.1 35.1 1.21 1.78 0.3200 0.1930
120 12.8 8.0 0.12 2.1 36.6 1.34 2.05 0.2530 0.1530
150 14.2 8.0 0.12 2.2 38.2 1.47 2.37 0.2060 0.1240
185 15.9 8.0 0.12 2.2 39.9 1.64 2.76 0.1640 0.0991
240 18.3 8.0 0.12 2.3 42.5 1.90 3.37 0.1250 0.0754
300 20.4 8.0 0.12 2.4 44.8 2.16 4.01 0.1000 0.0601
400 23.2 8.0 0.12 2.4 47.6 2.52 4.87 0.0778 0.0470
500 26.4 8.0 0.12 2.5 51.3 2.98 6.01 0.0605 0.0366
630 30.1 8.0 0.12 2.6 55.2 3.54 7.43 0.0469 0.0283

6)3.6/6(7.2)kV,3.6/6.6(7.2)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of
Copper Tape
Normal Thickness of Outer Sheath Approx.
Overall Dia.
Approx. Net Weight Max. D.C. Resistance of Conductor at 20ºC
Al Conductor Cu Conductor Al Conductor Cu Conductor
mm2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25 6.0 2.5 0.1 2.0 34.6 1.13 1.58 1.2000 0.7270
35 6.9 2.5 0.1 2.1 36.8 1.29 1.92 0.8680 0.5240
50 8.2 2.5 0.1 2.2 39.8 1.51 2.36 0.6410 0.3870
70 9.7 2.5 0.1 2.3 43.2 1.81 3.04 0.4430 0.2680
95 11.3 2.5 0.1 2.4 46.9 2.17 3.87 0.3200 0.1930
120 12.8 2.5 0.1 2.4 50.1 2.53 4.69 0.2530 0.1530
150 14.2 2.5 0.1 2.5 53.3 2.90 5.60 0.2060 0.1240
185 15.9 2.5 0.1 2.6 57.2 3.40 6.77 0.1640 0.0991
240 18.3 2.6 0.1 2.8 63.2 4.12 8.55 0.1250 0.0754
300 20.4 2.8 0.1 3.0 69.0 4.89 10.46 0.1000 0.0601
400 23.2 3.0 0.1 3.4 76.7 6.10 13.18 0.0778 0.0470
500 26.4 3.2 0.1 3.6 85.7 8.10 16.55 0.0605 0.0366

7)6/10(12)kV,6.35/11(12)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of
Copper Tape
Normal Thickness of Outer Sheath Approx.
Overall Dia.
Approx. Net Weight Max. D.C. Resistance of Conductor at 20ºC
Al Conductor Cu Conductor Al Conductor Cu Conductor
mm2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25 6.0 3.4 0.1 2.1 38.7 1.30 1.75 1.2000 0.7270
35 6.9 3.4 0.1 2.2 40.9 1.47 2.22 0.8680 0.5240
50 8.2 3.4 0.1 2.3 43.9 1.70 2.50 0.6410 0.3870
70 9.7 3.4 0.1 2.4 47.3 2.02 3.25 0.4430 0.2680
95 11.3 3.4 0.1 2.5 51.0 2.42 4.12 0.3200 0.1930
120 12.8 3.4 0.1 2.6 54.4 2.79 4.95 0.2530 0.1530
150 14.2 3.4 0.1 2.7 57.6 3.17 5.87 0.2060 0.1240
185 15.9 3.4 0.1 2.8 61.5 3.69 7.06 0.1640 0.0991
240 18.3 3.4 0.1 2.9 66.9 4.38 8.82 0.1250 0.0754
300 20.4 3.4 0.1 3.1 71.8 5.11 10.68 0.1000 0.0601
400 23.2 3.4 0.1 3.3 78.3 6.24 13.32 0.0778 0.0470
500 26.4 3.4 0.1 3.5 86.4 7.63 16.50 0.0605 0.0366

8)8.7/10(15)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of
Copper Tape
Normal Thickness of Outer Sheath Approx.
Overall Dia.
Approx. Net Weight Max. D.C. Resistance of Conductor at 20ºC
Al Conductor Cu Conductor Al Conductor Cu Conductor
mm2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25 6.0 4.5 0.1 2.3 43.9 1.57 2.02 0.9270 0.7270
35 6.9 4.5 0.1 2.4 46.0 1.75 2.38 0.6680 0.5240
50 8.2 4.5 0.1 2.4 48.8 2.00 2.85 0.4936 0.3870
70 9.7 4.5 0.1 2.5 52.3 2.34 3.57 0.3420 0.2680
95 11.3 4.5 0.1 2.6 55.9 2.75 4.45 0.2464 0.1930
120 12.8 4.5 0.1 2.7 59.4 3.16 5.32 0.1955 0.1530
150 14.2 4.5 0.1 2.8 62.6 3.57 6.27 0.1587 0.1240
185 15.9 4.5 0.1 2.9 66.4 4.07 7.45 0.1271 0.0991
240 18.3 4.5 0.1 3.1 72.0 4.82 9.25 0.0976 0.0754
300 20.4 4.5 0.1 3.3 77.0 5.71 11.28 0.0778 0.0601
400 23.2 4.5 0.1 3.4 83.2 6.78 13.86 0.0615 0.0470
500 26.4 4.5 0.1 3.5 91.1 8.20 17.32 0.0487 0.0366

9)12/20(24)kV, 12.7/22(24)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of
Copper Tape
Normal Thickness of Outer Sheath Approx.
Overall Dia.
Approx. Net Weight Max. D.C. Resistance of Conductor at 20ºC
Al Conductor Cu Conductor Al Conductor Cu Conductor
mm2 mm mm mm2 mm mm kg/m kg/m Ω/km Ω/km
25
35 6.9 5.5 0.1 2.4 50.3 2.00 2.63 0.8680 0.6680
50 8.2 5.5 0.1 2.5 53.3 2.26 3.11 0.6410 0.4936
70 9.7 5.5 0.1 2.6 56.8 2.62 3.85 0.4430 0.3420
95 11.3 5.5 0.1 2.8 60.6 3.07 4.77 0.3200 0.2464
120 12.8 5.5 0.1 2.9 64.1 3.49 5.65 0.2530 0.1955
150 14.2 5.5 0.1 3.0 67.3 3.91 6.61 0.2060 0.1587
185 15.9 5.5 0.1 3.1 71.2 4.44 7.81 0.1640 0.1271
240 18.3 5.5 0.1 3.3 76.8 5.21 9.64 0.1250 0.0976
300 20.4 5.5 0.1 3.3 81.3 6.10 11.66 0.1000 0.0778
400 23.2 5.5 0.1 3.5 87.7 7.20 14.28 0.0778 0.0615
500 26.4 5.5 0.1 3.8 96.0 9.15 17.80 0.0605 0.0487

10)18/30(36)kV,19/33(36)kV,Three Cores,Al or Cu/XLPE/CTS/PVC Unarmoured Power Cable

Normal Cross Section of Conductor Normal Diameter of Conductor Normal Thickness of Insulation Normal Thickness of
Copper Tape
Normal Thickness of Outer Sheath Approx.
Overall Dia.
Approx. Net Weight Max. D.C. Resistance of Conductor at 20ºC
Al Conductor Cu Conductor Al Conductor Cu Conductor
mm2 mm mm mm mm mm kg/m kg/m Ω/km Ω/km
25
35
50 8.2 8.0 0.1 2.9 64.9 3.02 3.87 0.6410 0.4936
70 9.7 8.0 0.1 3.0 68.4 3.42 4.65 0.4430 0.3420
95 11.3 8.0 0.1 3.1 72.0 3.89 5.59 0.3200 0.2464
120 12.8 8.0 0.1 3.3 75.7 4.39 6.54 0.2530 0.1955
150 14.2 8.0 0.1 3.3 78.7 4.85 7.55 0.2060 0.1587
185 15.9 8.0 0.1 3.4 82.6 5.42 8.79 0.1640 0.1271
240 18.3 8.0 0.1 3.5 88.0 6.22 10.66 0.1250 0.0976
300 20.4 8.0 0.1 3.7 92.9 7.20 12.77 0.1000 0.0778
400 23.2 8.0 0.1 3.9 99.3 8.38 15.46 0.0778 0.0615
500 26.4 8.0 0.1 4.2 107.6 10.15 18.85 0.0605 0.0487