21/35kvaluminum Conductor XLPE Insulated Steel Wire Armored Power Cable

 21/35kvaluminum Conductor XLPE Insulated Steel Wire Armored Power Cable

Produktdetails

Basis Info

Modell Nr.:YJLV32, YJLV42
Anwendung: Bau , U-Bahn , Industriell , Kraftwerk
Spannung: High Voltage Cable
Strom: DC-Kabel
Isoliermaterial: XLPE
Bescheinigung: ISO

Zusätzliche Informationen.

Warenzeichen:JYTOP
Verpackung:Packed in Reels
Standard:as per popular standards or clients's requirement
Herkunft:Zhengzhou, China
HS-Code:8544601200
Produktionskapazität:100km Per Month

Produktbeschreibung

HIGH VOLTAGE 21/35kv Aluminum Conductor XLPE Insulated Steel Wire Armored Power Cable

21/35kV AL/XLPE/SWA/PVC(or PE) Power Cable

1. Description
Construction: Compacted stranded circular aluminum conductor, extruded semi-conducting compound as conductor shield, cross-linked polyethylene (XLPE) insulation, semi-conducting compound as insulation shield, copper tape or combination of copper wire and tape as metallic screen, three cores assembled together with non-hygroscopic polypropylene filler, wrapped with binder tape, PVC inner covering as armoring bedding, galvanized steel wire armored, PVC or PE outer sheath.

2. Operating Characteristics
Rated voltage U0/U(Um): 21/35 (40.5)kV
U0 is the rated power frequency voltage between conductor and earth or metallic screen for which the cable is designed;
U is the rated power frequency voltage between conductors for which the cable is designed;
Um is the maximum value of the "highest system voltage" for which the equipment may be used.
Max. Permissible continuous operating temperature of conductor: 90 ° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed: 250 ° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 15 times of the diameter of cable
For three core cable: Not less than 12 times of the diameter of cable
When the armored single core cable used for Alternative Current(AC) system, the armoring material should be non-magnetic.

3. Application
The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, outdoors, in tunnel, in cable trench, or direct in ground, able to bear external mechanical force and certain pulling force.

4. Manufacturing Standards
IEC 60502-2 and Chinese National Standard GB/T 12706-2008 We can produce above cables according to popular international standards such as ASTM, BS, DIN, NF &AS/NZ also.

KINDLY NOTE: If you want to know more details about this kind of products, please visit our website:jytopcable for further information. Thanks.

Size Nominal thickness of XLPE insulation(mm) Approx. thickness of copper tape screen (mm) Approx. diameter of steel wire (mm) Nominal thickness of PVC or PE(mm) Approx. overall diameter of finished cable(mm) Max. conductor D.C resistance @ 20ºC (Ω/km)
3x50mm 2 9.3 0.10 3.15 3.6 85.4 0.641
3x70mm 2 9.3 0.10 3.15 3.7 89.3 0.443
3x95mm 2 9.3 0.10 3.15 3.8 93.2 0.320
3x120mm 2 9.3 0.10 3.15 3.9 96.7 0.253
3x150mm 2 9.3 0.10 3.15 4.0 100.4 0.206
3x185mm 2 9.3 0.10 3.15 4.2 104.5 0.164
3x240mm 2 9.3 0.10 3.15 4.3 110.2 0.125
3x300mm 2 9.3 0.10 3.15 4.5 115.2 0.100
3x400mm 2 9.3 0.10 3.15 4.7 122.8 0.0778